BuildMeter guide · Energy & Electrical

Heat-Recovery Ventilation Planning Guide

Plan balanced ventilation from required outdoor airflow and climate conditions. Includes measurement workflow, a worked example, decision table, ordering checkpoints, common failures and professional boundaries.

Liron Elimeleh Published July 30, 2026Last reviewed August 19, 2026

Direct answer

What to know first

Plan balanced ventilation from required outdoor airflow and climate conditions.

Open Heat Recovery Ventilator Calculator

Plan airflow and recovered heat as separate quantities

A heat-recovery ventilator (HRV) exchanges stale indoor air for outdoor air while transferring part of the temperature difference between the two air streams. The planning inputs are ventilation airflow, indoor/outdoor temperatures, sensible recovery efficiency and operating time—not packages or generic material allowance.

HRV planning inputs
InputMeaningWhy it matters
Outdoor-air flowcfm or L/sSets ventilation volume and fan duty
Temperature differenceIndoor minus outdoor temperatureSets sensible heating/cooling load
Sensible recovery efficiencyFraction of temperature load recoveredReduces ventilation heat loss
Run timeHours/day or duty cycleConverts rate to energy

Worked recovery example

Assume 100 cfm of outdoor air, indoor air at 70°F and outdoor air at 30°F, a 40°F temperature difference. Using the common sensible-air approximation 1.08 × cfm × ΔT, untreated ventilation would represent about 4,320 Btu/h of sensible heat. At 70% sensible recovery, roughly 3,024 Btu/h is recovered and about 1,296 Btu/h remains as ventilation heating load, before fan power and frosting/defrost effects.

Recommended workflow

  1. Establish the required outdoor-airflow basis for the home and local requirements.
  2. Use the Heat Recovery Ventilator Calculator to compare airflow, temperature difference and recovery efficiency.
  3. Check fan power and annual run time separately from recovered thermal energy.
  4. Verify duct size, balancing, intake/exhaust placement and condensate handling from the selected equipment instructions.

Common mistakes

  • Using advertised maximum airflow instead of the balanced design airflow.
  • Treating sensible recovery efficiency as total system efficiency in every climate condition.
  • Ignoring fan electricity when comparing annual energy impact.
  • Assuming an HRV replaces bathroom/range exhaust requirements or dehumidification strategy.

Professional limits

Ventilation rates, duct design, combustion safety, frost control and balancing require system-specific design and commissioning. The calculator is a planning model, not an HVAC design approval.

Sources